1-5. Limitation of compressor rotation number by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
E zone
D zone
C zone
B zone
A zone
14.0°F
(-10°C)
32.0°F
(0°C)
50.0°F
(10°C)
66.2°F
(19°C)
100.4°F
(38°C)
Model name Outdoor temperature zone
Limitation of compressor
frequency
AOUH09LPAS1
A zone 42 rps
B zone 42 rps
C zone 33 rps
D zone 28 rps
E zone 16 rps
F zone 21 rps
AOUH12LPAS1
A zone 35 rps
B zone 35 rps
C zone 35 rps
D zone 15 rps
E zone 15 rps
F zone 36 rps
1-5. Limitation of compressor rotation number by outdoor temperature - (04-6) - 1. Rotation number control of compressor