EasyManua.ls Logo

Fujitsu AOUH24LMAS1 - External Input

Fujitsu AOUH24LMAS1
215 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-1. External input
→ith using external input function, some functions on this product can be controlled from an external
device.
“Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
A twisted pair cable (22A→G) should be used. Maximum length of cable is 492 ft (150 m).
The wire connection should be separate from the power cable line.
¢
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit connectors.
1
2
3

Connector
(CN46)
PCB
Connected unit
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
2-1. External input - (05-13) - 2. External input and output
FIELD
WORKING
FIELD
WORKING

Table of Contents

Other manuals for Fujitsu AOUH24LMAS1

Related product manuals