4-2. Heating capacity
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
¢
Model: ASUH18LPAS
AFR CFM 506
Indoor temperature
°FDB 60 65 70 72 75
Outdoor temperature
°FDB °FWB
TC IP TC IP TC IP TC IP TC IP
kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW
5 3 19.63 2.40 19.11 2.45 18.60 2.50 18.09 2.55 17.57 2.60
14 12 20.89 2.08 20.35 2.12 19.80 2.17 19.25 2.21 18.71 2.25
23 19 21.78 2.01 21.21 2.05 20.64 2.09 20.07 2.13 19.50 2.17
32 28 21.91 1.91 21.33 1.95 20.76 1.99 20.19 2.03 19.61 2.07
41 37 24.06 1.96 23.43 2.00 22.80 2.04 22.17 2.08 21.54 2.12
47 43 25.33 2.02 24.66 2.06 24.00 2.10 23.34 2.14 22.67 2.18
50 47 27.98 2.04 27.25 2.09 26.52 2.13 24.77 2.17 24.77 2.21
59 50 29.00 2.05 28.24 2.09 27.48 2.14 24.77 2.18 24.77 2.22
68 59 25.99 1.68 25.31 1.71 24.63 1.75 23.95 1.78 23.27 1.82
75 64 26.14 1.53 25.45 1.56 24.77 1.59 24.09 1.62 23.40 1.65
AFR
m
3
/h
860
Indoor temperature
°CDB 15.6 18.3 21.1 22.2 23.9
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15.0 -16.1 5.75 2.40 5.60 2.45 5.45 2.50 5.30 2.55 5.15 2.60
-10.0 -11.1 6.12 2.08 5.96 2.12 5.80 2.17 5.64 2.21 5.48 2.25
-5.0 -7.2 6.38 2.01 6.22 2.05 6.05 2.09 5.88 2.13 5.72 2.17
0.0 -2.2 6.42 1.91 6.25 1.95 6.08 1.99 5.92 2.03 5.75 2.07
5.0 2.8 7.05 1.96 6.87 2.00 6.68 2.04 6.50 2.08 6.31 2.12
8.3 6.1 7.42 2.02 7.23 2.06 7.03 2.10 6.84 2.14 6.65 2.18
10.0 8.3 8.20 2.04 7.99 2.09 7.77 2.13 7.26 2.17 7.26 2.21
15.0 10.0 8.50 2.05 8.28 2.09 8.05 2.14 7.26 2.18 7.26 2.22
20.0 15.0 7.62 1.68 7.42 1.71 7.22 1.75 7.02 1.78 6.82 1.82
24.0 18.0 7.66 1.53 7.46 1.56 7.26 1.59 7.06 1.62 6.86 1.65
¢
Model: ASUH24LPAS
AFR CFM 594
Indoor temperature
°FDB 60 65 70 72 75
Outdoor temperature
°FDB °FWB
TC IP TC IP TC IP TC IP TC IP
kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW
5 3 20.58 2.74 20.04 2.79 19.50 2.85 18.96 2.90 18.42 2.96
14 12 25.27 3.07 24.61 3.13 23.95 3.20 23.29 3.26 22.63 3.32
23 19 26.30 2.97 25.61 3.03 24.92 3.09 24.23 3.15 23.54 3.21
32 28 26.52 2.81 25.82 2.87 25.13 2.93 24.44 2.99 23.74 3.04
41 37 29.02 2.88 28.26 2.94 27.50 3.00 26.74 3.06 25.98 3.11
47 43 30.60 2.98 29.80 3.03 29.00 3.10 28.20 3.16 27.40 3.22
50 47 33.78 3.02 32.89 3.08 32.01 3.15 29.92 3.21 29.92 3.27
59 50 35.14 3.03 34.22 3.09 33.30 3.16 29.92 3.22 29.92 3.28
68 59 31.39 2.27 30.57 2.31 29.75 2.36 28.93 2.41 28.11 2.45
75 64 31.57 2.05 30.75 2.09 29.92 2.14 29.09 2.18 28.27 2.22
AFR
m
3
/h
1,010
Indoor temperature
°CDB 15.6 18.3 21.1 22.2 23.9
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15.0 -16.1 6.03 2.74 5.87 2.79 5.72 2.85 5.56 2.90 5.40 2.96
-10.0 -11.1 7.41 3.07 7.21 3.13 7.02 3.20 6.83 3.26 6.63 3.32
-5.0 -7.2 7.71 2.97 7.51 3.03 7.30 3.09 7.10 3.15 6.90 3.21
0.0 -2.2 7.77 2.81 7.57 2.87 7.37 2.93 7.16 2.99 6.96 3.04
5.0 2.8 8.51 2.88 8.28 2.94 8.06 3.00 7.84 3.06 7.61 3.11
8.3 6.1 8.97 2.98 8.73 3.03 8.50 3.10 8.26 3.16 8.03 3.22
10.0 8.3 9.90 3.02 9.64 3.08 9.38 3.15 8.77 3.21 8.77 3.27
15.0 10.0 10.30 3.03 10.03 3.09 9.76 3.16 8.77 3.22 8.77 3.28
20.0 15.0 9.20 2.27 8.96 2.31 8.72 2.36 8.48 2.41 8.24 2.45
24.0 18.0 9.25 2.05 9.01 2.09 8.77 2.14 8.53 2.18 8.28 2.22
- 9 -
4-2. Heating capacity 4. Capacity table
WALL MOUNTED
ASUH18-24LPAS
WALL MOUNTED
ASUH18-24LPAS