6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Models: AOUH18LPAS1 and AOUH24LPAS1
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5 7.5 10 15 20
ft 16 25 33 49 66
Height difference H
Indoor unit is higher than outdoor
unit *1
15 49 - - - 0.951 0.950
10 33 - - 0.979 0.967 0.966
7.5 25 - 0.988 0.983 0.971 0.970
5 16 0.994 0.992 0.987 0.975 0.974
0 0 1.002 1.000 0.995 0.983 0.982
Indoor unit is lower than outdoor
unit *2
-5 -16 1.002 1.000 0.995 0.983 0.982
-7.5 -25 - 1.000 0.995 0.983 0.982
-10 -33 - - 0.995 0.983 0.982
-15 -49 - - - 0.983 0.982
HEATING
Pipe length
m
5 7.5 10 15 20
ft 16 25 33 49 66
Height difference H
Indoor unit is higher than outdoor
unit *1
15 49 - - - 0.994 0.979
10 33 - - 1.012 0.994 0.979
7.5 25 - 1.000 1.012 0.994 0.979
5 16 0.969 1.000 1.012 0.994 0.979
0 0 0.969 1.000 1.012 0.994 0.979
Indoor unit is lower than outdoor
unit *2
-5 -16 0.964 0.995 1.007 0.989 0.974
-7.5 -25 - 0.993 1.004 0.986 0.972
-10 -33 - - 1.002 0.984 0.969
-15 -49 - - - 0.974 0.959
- 71 -
6-1. Models: AOUH18LPAS1 and AOUH24LPAS1 6. Capacity compensation rate for pipe length and height difference