1-3. Dry operation
The rotation number of the compressor shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the table below.
Zone is defined by set temperature and room temperature.
¢ Compact cassette type
Rotation number range of compressor
Unit: rps
Model: AOYG18KBTA3
Model name Outdoor temperature zone Operating rotation number
AUXG07–12KVLA
X zone 54
J zone 54
Y zone 0
AUXG14KVLA
X zone 46
J zone 46
Y zone 0
Model: AOYG24KBTA3
Model name Outdoor temperature zone Operating rotation number
AUXG07–12KVLA
X zone 54
J zone 54
Y zone 0
AUXG14–18KVLA
X zone 46
J zone 46
Y zone 0
Compressor control based on room temperature
Ts+0.5°C
Ts -1.5°C
Ts-0.5°C
Ts+1.5°C
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
1-3. Dry operation - (04-11) - 1. Rotation number control of compressor