7-5. Fresh air control
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as below.
Operation
Stop
Operation
Stop
Fan motor
(Indoor unit)
Fan motor
(for Fresh Air)
7-6. Compressor preheating
By preheating the compressor, warm airflow is quickly discharged when the operation is started.
Models: AOYG18KBTB, AOYG22KBTB, and AOYG24KBTB
Triggering condition
30 minutes after compressor stopped.
Outdoor unit heat exchanger temperature (Tn)
-2°C
Off
On
Tn
Tn
-4°C
When the jumper wire (JM2) is disconnected:
5°C
Off
On
Tn
Tn
7°C
Models: AOYG30KBTB, AOYG36KBTB, and AOYG45KBTB
Triggering condition 1
Outdoor temperature ≤ 20°C
When outdoor temperature reaches 26°C, compressor preheating stops.
30 minutes after compressor stopped
Triggering condition 2
0°C
Off
On
Tn
Tn
2°C
Tn: Outdoor unit heat exchanger temp.