1-5. Compressor frequency limitation by outdoor temperature
The minimum compressor frequency is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
13°C
E zone
7°C
D zone
°C
C zone
B zone
A zone
-5
2
°C
-10°C
G zone
21°C
J zone
50°C
K zone
52°C
H zone
31°C
I zone
46°C
Model name Outdoor temperature zone
Limitation of compressor
frequency
AOYG36KQTA
A zone 55 rps
B zone 52 rps
C zone 47 rps
D zone 39 rps
E zone 33 rps
F zone 25 rps
G zone 18 rps
H zone 20 rps
I zone 20 rps
J zone 21 rps
K zone 24 rps
AOYG45KQTA
A zone 60 rps
B zone 57 rps
C zone 48 rps
D zone 36 rps
E zone 27 rps
F zone 24 rps
G zone 20 rps
H zone 20 rps
I zone 20 rps
J zone 26 rps
K zone 30 rps
1-5. Compressor frequency limitation by outdoor temperature - (04-7) - 1. Compressor frequency control