- 64 -
DUCT TYPE
ARYG12-54LHTBP
Forced thermostat off function
Control output function
The output is low when the unit is stopped.
Function
setting /
Rotary SW of External
input and output PCB
External input Input signal Command
60-00 / 2
External input and output
PCB
Input 1
Off On
Thermostat
off
60-09 / B
60-10 / C
On Off
Normal
operation
60-11 / D
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-00 / 1, 2 Output of indoor unit CN47
Low High Operation
High Low Stop
60-00 / 1
External input and output
PCB
Output 1
Off On Operation
60-09 / B
60-10 / C
On Off Stop
60-11 / D
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
Operation
Stop
High
Low
CN47
On
Off
Output 1
Indoor unit