1-6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the fan speed of the outdoor unit.
(Table 6 : Fan speed of the outdoor unit)
Upper fan
Lower fan
Upper fan
Lower fan
The outdoor fan speed is decided depending on the compressor and the outdoor temperature.
The compressor and the fan start-up at the same time,
and the fan stops after the compressor stops and 60 seconds has passed.
The fan doesn't operates for 10 seconds after the fan stops.
The upper fan and the lower fan operates at 500 rpm for 20 seconds after the start-up.
However, the fan operates at 200rpm when the initial rotation speed is 300rpm or less.
Cooling
850/ 780/ 520/ 480/ 400/ 350/ 280 rpm
800/ 750/ 520/ 350/ 280/ 0 rpm
900/ 850/ 780/ 520/ 480/ 400/ 350/ 280 rpm
800/ 750/ 520/ 350/ 280/ 0 rpm
AO *G36/ 45LATT
01-10
AO *G54LATT
AOTG60LATT
Upper fan
Lower fan
Upper fan
Lower fan
Heating
870/ 780/ 520/ 350/ 200/ 170/ 150 rpm
840/ 750/ 520/ 350/ 200/ 170/ 150 rpm
900/ 870/ 780/ 520/ 350/ 200/ 170/ 150 rpm
900/ 840/ 750/ 520/ 350/ 200/ 170/ 150 rpm
AO *G36/ 45LATT
AO *G54LATT
AOTG60LATT
.
.
.
.
.

Table of Contents

Other manuals for Fujitsu ARTG45LHTB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARTG45LHTB and is the answer not in the manual?

Fujitsu ARTG45LHTB Specifications

General IconGeneral
BrandFujitsu
ModelARTG45LHTB
CategoryAir Conditioner
LanguageEnglish

Related product manuals