02 - 07
)
-
OUTDOOR UNIT
AOU36R
OUTDOOR UNIT
AOU36R
This table is created using the maximum capacity.
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
INDOOR UNIT 12000BTU (AOU36R)
Height difference H
5m 7.5m 10m 15m 20m 25m
16ft. 25ft. 33ft. 49ft. 66ft. 82ft.
15m 49ft. - - -
0.982 0.966 0.947
10m 33ft. - -
0.995 0.982 0.966 0.947
7.5m 25ft. -
1.000 0.995 0.982 0.966 0.947
5m 16ft.
1.003 1.000 0.995 0.982 0.966 0.947
0m 0ft. 1.003 1.000 0.995 0.982 0.966 0.947
-5m -16ft.
0.995 0.992 0.987 0.975 0.958 0.939
-7.5m -25ft. -
0.988 0.983 0.971 0.954 0.935
-10m -33ft. - -
0.979 0.967 0.950 0.931
-15m -49ft. - - -
0.959 0.943 0.924
Pipe length
COOLING
Height difference H
1
2
5m 7.5m 10m 15m 20m 25m
16ft. 25ft. 33ft. 49ft. 66ft. 82ft.
15m 49ft. - - -
0.959 0.912 0.888
10m 33ft. - -
0.984 0.964 0.917 0.892
7.5m 25ft. -
0.993 0.987 0.966 0.919 0.894
5m 16ft.
0.998 0.995 0.989 0.969 0.921 0.897
0m 0ft. 1.003 1.000 0.994 0.974 0.926 0.901
-5m -16ft.
1.003 1.000 0.994 0.974 0.926 0.901
-7.5m -25ft. -
1.000 0.994 0.974 0.926 0.901
-10m -33ft. - -
0.994 0.974 0.926 0.901
-15m -49ft. - - -
0.974 0.926 0.901
HEATING
Height difference H
1
2
Pipe length
Indoor unit
Connection pipe
H
Outdoor unit
Indoor unit is upper than outdoor unit.
1
Indoor unit
Connection pipe
H
Outdoor unit
Indoor unit is under than outdoor unit.
2
Indoor unit is under
than outdoor unit
Indoor unit is upper
than outdoor unit
Indoor unit is under
than outdoor unit
Indoor unit is upper
than outdoor unit