Trouble shooting 30
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check connection of around the Compressor components
OKOK
OKOK
Indicate or Display:
Check Point 3: Replace Main PCB
Outdoor unit Main PCB
Compressor
Compressor rotor position
detection error
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
If Check Point 1,2 do not improve the symptom, change Main PCB.
Check if connector is removed.
Check erroneous connection.
Check if cable is open. (Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
For Compressor Terminal, Main PCB
"Protection stop by "overcurrent generation at inverter compressor starting"
restart" generated consecutively 50 times x 3 sets (total 150 times)
02-31
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OKOK
Check Point 4: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
Error code : 95
Outdoor unit : No indication

Table of Contents

Other manuals for Fujitsu ARXG14KSLAP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG14KSLAP and is the answer not in the manual?

Fujitsu ARXG14KSLAP Specifications

General IconGeneral
BrandFujitsu
ModelARXG14KSLAP
CategoryAir Conditioner
LanguageEnglish

Related product manuals