Multiple outdoor unit installation
When the upper space is open:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the front only.
300
or more
250 or more
1,500 or more
250 or more
When there are obstacles at the front and
rear.
500 or more
1,500 or more
250 or
more
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear and above.
1,500 or more
500 or more
250 or more
250 or more
Max. 300
1,500 or more
- 37 -
3-1. Models: AOYG45KRTA and AOYG54KRTA 3. Installation space