7) Cold air prevention
This setting is to disable the cold air prevention function during heating operation. When disabled,
the fan setting will always follow the setting on the remote controller. (Excluding defrost mode)
Function number Setting value Setting description Factory setting
43
00 Enable
01 Disable
8) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number Setting value Setting description Factory setting
44
00 A
01 B
02 C
03 D
9) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number Setting value Setting description Factory setting
46
00 Operation/Stop mode 1
01 (Setting prohibited)
02 Forced stop mode
03 Operation/Stop mode 2
10) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired re-
mote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is possi-
ble by setting function setting 30 and 31 too.
Function number Setting value Setting description Factory setting
48
00 Both
01 Wired remote controller
- 46 -
12-2. Function settings by using remote controller 12. Function settings
DUCT TYPE
ARYG72-90LHTA
DUCT TYPE
ARYG72-90LHTA