12. External input and output
With using external input and output functions, this product can be operated inter-connectedly with
an external device.
Connector Input Output Remarks
CN131 Low noise mode
See external input/output settings
for details.
CN132 Peak cut mode
CN136 Error status
CN137 Compressor status
12-1. External input
With using external input function, on/off status of “Low noise mode” and “Peak cut mode” can be
specified by the external signal.
¢
Low noise mode
In following condition, the operating noise of the outdoor unit reduces comparing from the one in nor-
mal operating condition:
The air conditioner is set to the “Low noise mode” when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
NOTE:
Product performance may drop depending on some conditions such as the outdoor temper-
ature.
Circuit diagram example (CN131)
Outdoor unit
control PCB
Connected unit
Example: Switch
Signal
*10 m
Connector
Locally purchased
CN131
Contact capacity: DC 24 V or more, 10 mA or more.
*: Make the distance from the PCB to the connected
unit within 10 m.
Construct a circuit as shown in this figure with using
optional parts mentioned below.
Input signal: On in “Low noise mode”
Input signal: Off in normal operation
To set the level of “Low noise mode”, refer to "Low
noise mode" on page 75.
On
Off
On
Off
Input signal
Low noise mode
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
- 69 -
12-1. External input 12. External input and output
OUTDOOR UNIT
AOYG72-90LRLA
OUTDOOR UNIT
AOYG72-90LRLA