Compressor status output
Signal on compressor operation status is generated when the compressor is running.
Circuit diagram example (CN137)
Signal
Outdoor unit
control PCB
Connected unit
Connector
1
2
Locally purchased
*10 m
Vcc
+
+
-
Load
Vcc
Power
supply
CN137
1: Power supply
Voltage (Vcc): DC 24 V or less
2: Load
DC 500 mA or less
*: Make the distance from the PCB to the con-
nected unit within 10 m.
Operation
Stop
On
Off
Compressor
status
Output signal
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
- 72 -
12-2. External output 12. External input and output
OUTDOOR UNIT