Error status
The output is ON when an error is generated for the indoor unit.
Indoor unit fan operation status
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-09 / B Output of indoor unit CN47
Low → High Error
High → Low Normal
60-00 / 2
External input and output
PCB
Output 1
Off → On Error
On → Off Normal
60-00 / 1
Output 2
Off → On Error
nOC / 01-06 → Off Normal
3 tuptuOD / 11-06
Off → On Error
On → Off Normal
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-10 / C Output of indoor unit CN47
Low → High Fan run
High → Low Fan stop
60-00 / 2
External input and output
PCB
Output 2
Off → On Fan run
60-09 / B
On → Off Fan stop
60-11 / D
3 tuptuO1 / 00-06
Off → On Fan run
On → Off Fan stop
Output signal Condition
On
The indoor unit fan is operating.
Low → High
Off The fan is stopped or during cold air prevention.
High → Low During thermostat off when in dry mode operation.
Normal
High
Low
CN47
On
Indoor unit
Fan stop
High
Low
CN47
On
Output 2, 3
03-19