03-04
Setting Description Function Number Setting Value
Enable
Disable
43
00
01
( Factory setting)
Setting Description Function Number Setting Value
Both
Wired remote controller
48
00
01
( Factory setting)
Setting Description Function Number Setting Value
Operation/Stop mode 1
Operation/Stop mode 2
(Setting prohibited)
46
00
01
20edom pots decroF
03
( Factory setting)
Cold air prevention
This setting is to disable the cold air prevention function during heating operation. When
disabled, the fan setting will always follow the setting on the remote controller. (Excluding
defrost mode)
External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
Setting Description Function Number Setting Value
Operation status
Auxiliary heater
Error status
60
00
09
10Fresh air control
11
( Factory setting)
Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
“Wired remote controller” (01). This function will only work if the function setting 42 is set
at “Both” (01)
Indoor unit fan control for energy saving for cooling
( Factory setting)
Setting Description Function Number Setting Value
Disable
Enable
Remote controller
49
02
00
01
Enables or disables the power-saving function by controlling the indoor unit fan rotation
when the outdoor unit is stopped during cooling operation.
00 : When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01 : When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02 : Enable or disable this function by remote controller setting.
Switching functions for external output terminal
Functions of the external output terminal can be switched.
NOTES:
・As the factory setting, this setting is initially inactivated.
・Set to “00” or “01” when connecting a remote controller that cannot set the Fan control for
energy saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each
remote controller.