3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
(Not defrosted for 10 minutes)
Heating operation start : Compressor ON
Outdoor HEX temp.: Over 16°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
Outdoor HEX temp.
Below - 17°C
Outdoor HEX temp.
- Outside air temp.
Below - 7°C
or
Outdoor HEX temp.
Below - 20°C
Integrating defrost
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Defrost start
Normal defrost
Outside air temp. > -10°C Outside air temp. < -10°C
=
Compressor
OFF count :
40 times
(Less than 10min.)
Compressor
integrating
operation:
Over 240 min.
Outdoor
heat exchanger
temperature:
Below - 3°C
Compressor
integrating
operation:
Over 213 min.
Outdoor
heat exchanger
temperature:
Below - 5°C
Intermittent operation Continuous operation
Compressor
integrating
operation:
Over 210 min. &
Stopped
Outdoor
heat exchanger
temperature:
Below - 2°C

Other manuals for Fujitsu AS G07LLCC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AS G07LLCC Series and is the answer not in the manual?

Fujitsu AS G07LLCC Series Specifications

General IconGeneral
BrandFujitsu
ModelAS G07LLCC Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals