Trouble shooting 6
INDOOR UNIT
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
62.9102.1131.4170.7223.3295.1Resistance Value (k )
Temperature
OKOK
OK
17.125.639.7Resistance Value (k )
Temperature
Indoor unit Heat Ex. middle temp.
sensor error
Indoor unit Controller PCB
Heat Ex. temperature thermistor
When Heat Ex. temperature thermistor open or short-circuit is detected.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
02-07
20°C10°C5°C0°C-5°C-10°C
50°C
11.6
60°C
10.4
63°C40°C30°C
Indicate or Display:
Refer to error code table.
THERMISTOR
(ROOM TEMP.)
THERMISTOR
(PIPE)
BLACK
CN4
1
2
3
4
1
2
3
4
BLACK
BLACK
BLACK
-20°C
-15°C
526.8
392.1

Other manuals for Fujitsu AS G07LLCC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AS G07LLCC Series and is the answer not in the manual?

Fujitsu AS G07LLCC Series Specifications

General IconGeneral
BrandFujitsu
ModelAS G07LLCC Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals