Trouble shooting 11
INDOOR UNIT
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
64.22102.5130.9168.6218.6286.3503.5920.3Resistance Value (k )
Temperature
OKOK
OKOK
41.3
2.03.44.66.48.9Resistance Value (k )
Temperature
Discharge temp. sensor error
Outdoor unit Main PCB
Discharge pipe temperature thermistor
When Discharge pipe temperature thermistor open or short-circuit
is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-12
90°C80°C70°C
27.3
40°C
18.4
50°C
12.7
60°C
30°C
100°C
2.6
110°C
5°C0°C-5°C-10°C-20°C-30°C
20°C10°C
120°C
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
1
2
3
4
1
2
3
4
1
2
3
1
2
3
CN71
CN70
Indicate or Display:
Refer to error code table.