EasyManuals Logo

Fujitsu AS G07LMCA Series User Manual

Fujitsu AS G07LMCA Series
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
Trouble shooting 13
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
26.534.645.460.280.6109.0Resistance Value (k )
Temperature
OKOK
OKOK
20.6
6.48.010.012.316.0Resistance Value (k )
Temperature
Outdoor temp. sensor error
Outdoor unit Main PCB
Outdoor temperature thermistor
When Outdoor temperature thermistor open or short-circuit is
detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-14
-15°C-20°C
205.7
-30°C
148.8
-25°C
35°C
5.2
40°C
4.2
45°C
3.5
50°C
2.8
55°C30°C25°C
10°C5°C0°C-5°C-10°C
20°C15°C
Indicate or Display:
Refer to error code table.
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
1
2
3
4
1
2
3
4
1
2
3
1
2
3
CN71
CN70

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AS G07LMCA Series and is the answer not in the manual?

Fujitsu AS G07LMCA Series Specifications

General IconGeneral
BrandFujitsu
ModelAS G07LMCA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals