EasyManua.ls Logo

Fujitsu ASU12RLF - Outdoor Unit Main PCB Error

Fujitsu ASU12RLF
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Replace Main PCB
YESYES
NO
Trouble shooting 8
OUTDOOR UNIT Error Method:
Indicate or Display:
Indicate or Display:
Outdoor unit main PCB error
Outdoor unit Main PCB
1. External cause (Noise, temporary open, voltage drop) 2. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related
cables near the power line.
Change Main PCB.
Access to EEPROM failed due to some cause after outdoor unit started.
02-12
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 6 times Flash, Timer lamp: 2 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 62]

Table of Contents

Other manuals for Fujitsu ASU12RLF

Related product manuals