5. OUTDOOR FAN CONTROL
The Table 6 shows the fan speed of the outdoor unit.
01-16
1. Outdoor Fan Motor
*
It runs at 500rpm for 20 seconds after starting up the outdoor fan.
When the outdoor heat exchanger temperature is lower than 2°F(1°C),
the fan speed switches to 780rpm on heating mode.
When the outdoor heat exchanger temperature is lower than 4°F(2°C),
the fan speed switches to 900rpm on heating mode.
( Table 6 : Fan speed of the outdoor unit )
780/ 730/ 400/ 300/ 250/ 200 rpm
780/ 730/ 660/ 400/ 300/ 250/ 200 rpm
Cooling
Heating
AOU18RLXFZ
AOU24RLXFZ
AOU36RLXFZ
850/ 780/ 400/ 300/ 200 rpm
900/ 780/ 400/ 300/ 200 rpm
(AOU18 / 24RLXFZ)
(AOU36RLXFZ)