2-14. E: 41. Room temperature sensor error (Indoor unit)
Indicator Indoor unit
Operation indicator 4 time flash
Timer indicator 1 time flash
Economy indicator Continuous flash
Error code E: 41
Detective actuator
Indoor unit main PCB
Room temperature thermistor is open or short is
detected always.
Room temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
• Check if connector is loose or removed.
• Check erroneous connection.
• Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
• For the room thermistor resistance value, refer to "Thermistor resistance values"
on page 03-100.
• If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of each indoor unit and check terminal voltage at thermis-
tor (DC 5.0 V).
NOTE: For details of thermistor connector, refer to "Wiring diagrams" in Chapter 2.
TECHNICAL DATA AND PARTS LIST on page 02-121.
If the voltage does not appear, replace main PCB.
↓
End
2-14. E: 41. Room temperature sensor error (Indoor unit) - (03-40) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ASY50-KM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASY50-KM and is the answer not in the manual?

Fujitsu ASY50-KM Specifications

General IconGeneral
BrandFujitsu
ModelASY50-KM
CategoryAir Conditioner
LanguageEnglish

Related product manuals