Fig.1 Outdoor temperature zone
2. COOLING OPEARTION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between set temperature and present room temperature, and
controls the operation frequency of the compressor.
Minimum
frequency
Maximum
frequency
AOYG09KMCBN
AOYG12KMCBN
AOYG14KMCBN
8 rps 46 rps
8 rps
68 rps
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Indoor fan mode
Me Lo Quiet
A zone 46 rps
B zone 46 rps
C zone 46 rps
AOYG09KMCBN
D zone 36 rps
E zone 36 rps
F zone 36 rps
34 rps
34 rps
34 rps
32 rps
32 rps
32 rps
30 rps
30 rps
30 rps
28 rps
28 rps
28 rps
20 rps
20 rps
20 rps
20 rps
20 rps
20 rps
01-02
E zone
F zone
10°C
0°C
12°C
2°C
When the room temperature is between +2°C to -2.5°C of the set temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
If the room temperature is some degrees lower than set temperature,
the compressor will be stopped.
Outdoor
temperature drops
Outdoor
Table.1
temperature rises
Limit of maximum speed based on outdoor temperature
Outdoor
temp. zone
Hi
Indoor fan mode
Me Lo Quiet
A zone 80 rps
B zone 80 rps
C zone 80 rps
AOYG14KMCBN
D zone 58 rps
E zone 58 rps
F zone 58 rps
50 rps
50 rps
50 rps
39 rps
39 rps
39 rps
42 rps
42 rps
42 rps
28 rps
28 rps
28 rps
26 rps
26 rps
26 rps
20 rps
20 rps
20 rps
Outdoor
temp. zone
Hi
Indoor fan mode
Me Lo Quiet
A zone 68 rps
B zone 68 rps
C zone 68 rps
AOYG12KMCBN
D zone 46 rps
E zone 46 rps
F zone 46 rps
42 rps
42 rps
42 rps
34 rps
34 rps
34 rps
36 rps
36 rps
36 rps
28 rps
28 rps
28 rps
22 rps
22 rps
22 rps
20 rps
20 rps
20 rps
Outdoor
temp. zone
Hi
If the room temperature is 2°C higher than set temperature, the compressor operation
frequency will attain to maximum performance.
8 rps
80 rps