Installation space requirement
1,000
or more
1,000
or more
1,800
or more
262
or more
Strong and durable ceiling
Obstruction
Floor
Unit: mm
Maximum height from floor to ceiling (Unit: mm)
07 and 09 models 12 or larger models
Standard 2,700
High ceiling 3,000
3-way direction setting:
100 or more*
Unit: mm
NOTES:
To set “3-direction”, optional Air outlet shutter plate (UTR-YDZB) must be installed, and the “out-
let-direction” need to be switched to “3-way” by remote controller.
*When installing the indoor unit, be careful about the maintenance space.
In 3-way outlet mode, changing of ceiling height setting by function setting 20 is prohibited.
(Ceiling height setting [function setting 20] is allowed to be changed only in 4-way outlet mode.)