Grating
PROHIBITED
WARNING
The appliance shall be installed, operated and stored in a room with a floor area larger than X
m
2
.
Amount of refrigerant charge
M (kg)
Minimum room area
X (m
2
)
M ≤ 1.22 -
1.22 < M ≤ 1.23 12.99
1.23 < M ≤ 1.50 19.31
1.50 < M ≤ 1.75 26.28
1.75 < M ≤ 2.0 34.33
2.0 < M ≤ 2.5 53.63
2.5 < M ≤ 3.0 77.23
3.0 < M ≤ 3.5 105.12
3.5 < M ≤ 4.0 137.29
(IEC 60335-2-40)