Forced stop
• In the case of "Edge" input
Function
setting
External Input and
Output PCB
External input Input signal Command
Rotary
switch
SW2
46-02
— Input of indoor unit Terminal
Off → On
Forced stop
(R.C. disabled)
On → Off
Normal
(R.C. enabled)
1 Edge
External Input and
Output PCB
Ex IN 1
Off → On
Forced stop
(R.C. disabled)
On → Off
Normal
(R.C. enabled)
On
Off
Forced stop
Normal
Remote controller
On On
Indoor unit operation
On
Ex IN 1
On
Off
• In the case of "Pulse" input
Function
setting
External Input and
Output PCB
External input Input signal Command
Rotary
switch
SW2
46-02 1 Pulse
External Input and
Output PCB
Ex IN 1
Pulse
Forced stop
(R.C. disabled)
Ex IN 2
Normal
(R.C. enabled)
On
Off
Remote controller
On
Off
Forced stop
Normal
Ex IN 1
Ex IN 2
On On On
Indoor unit operation
On
Off
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the remote
controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
- 192 -
12-1. Compact cassette type, Medium static pressure duct type (ARXH22KMTAP), and
Ceiling type
12. External input and output
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE

Table of Contents

Other manuals for Fujitsu ASYG14KMCC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG14KMCC and is the answer not in the manual?

Fujitsu ASYG14KMCC Specifications

General IconGeneral
BrandFujitsu
ModelASYG14KMCC
CategoryAir Conditioner
LanguageEnglish

Related product manuals