Heat pump prohibition control
Perform heating by external heater only. Indoor unit is continuous thermostat off.
• Compact cassette type
Operation Condition
Heater on
Heater is on as shown in following diagram of heating
temperature.
Heater off
• Heater is off as shown in following diagram of heating
temperature.
• Other than heating mode
• Error occurred
• Forced thermostat off
• Slim duct type
Operation Condition
Heater on
Heater is on as shown in following diagram of heating
temperature.
Heater off
DIP-SW101-3 On • Heater is off as shown in following diagram of heating
temperature.
• Other than heating mode
• Error occurred
• Forced thermostat off
• Fan stop protection
Indoor unit fan
setting for
external heater
Enabled
DIP-SW101-3 Off • Heater is off as shown in following diagram of heating
temperature.
• Other than heating mode
• Error occurred
• Forced thermostat off
Indoor unit fan
setting for
external heater
Disabled
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts
Tr-Ts (=Thon) ≤ -0.5°C
Tr-Ts ≥ 0.5°C
- 235 -
12-5. Wall mounted type (KGTE, KGTF, KMTE, KMCE, KMCF, KETE, KETE-B, KETF, and
KETF-B)
12. External input and output
4-5 UNIT
MULTI-SPLIT TYPE