Trouble shooting 6
INDOOR UNIT
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
62.9103.3134.2176.0233.2312.3579.61131.9Resistance Value (k )
Temperature
OKOK
OK
17.125.639.6Resistance Value (k )
Temperature
Indoor unit Heat Ex. sensor error
Indoor unit Controller PCB
Heat Ex. temperature thermistor
When Heat Ex. Temperature Thermistor open or short-circuit is detected.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
02-09
20°C10°C5°C0°C-5°C-10°C-20°C-30°C
50°C
11.6
60°C
10.4
63°C40°C30°C
Indicate or Display:
Refer to error code table.
THERMISTOR
(ROOM TEMP.)
THERMISTOR
(PIPE)
BLACK
CN4
1
2
3
4
1
2
3
4
BLACK
BLACK
BLACK

Other manuals for Fujitsu ASYG14LECA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG14LECA and is the answer not in the manual?

Fujitsu ASYG14LECA Specifications

General IconGeneral
BrandFujitsu
ModelASYG14LECA
CategoryAir Conditioner
LanguageEnglish

Related product manuals