EasyManua.ls Logo

Fujitsu AUU18RGLX - Installation Space Requirement

Fujitsu AUU18RGLX
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-3. Installation space requirement
Provide sufficient installation space for product safety.
For 4-direction setting:
Models: AUU18RGLX and AUU24RGLX
60 (1,500)
or more
40
(1,000) or more
71 (1,800) or more
Obstruction
119 (3,000) or more
Strong and durable ceiling
Floor
Ceiling height
Ceiling mode* “Low” : 107 (2,700)
Ceiling mode “Standard” : up to 119 (3,000)
Ceiling mode “High” : up to 138 (3,500)
11 (256) or more
Unit: in (mm)
Models: AUU30RGLX, AUU36RGLX, AUU42RGLX, and AUU48RGLX
60 (1,500)
or more
40
(1,000) or more
71 (1,800) or more
Obstruction
119 (3,000) or more
Strong and durable ceiling
Floor
Ceiling height
Ceiling mode* “Low” : 107 (2,700)
Ceiling mode “Standard” : up to 126 (3,200)
Ceiling mode “High” : up to 166 (4,200)
12 (298) or more
Unit: in (mm)
*: For switching the ceiling mode, refer to "Contents of function setting" on page 69.
- 8 -