16) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to “External heater output” on page 2.
Function number Setting value Setting description Factory setting
66
00 -4.0 °F (-20 °C)
01 -0.4 °F (-18 °C)
02 3.2 °F (-16 °C)
03 6.8 °F (-14 °C)
04 10.4 °F (-12 °C)
05 14.0°F (-10 °C)
06 17.6 °F (-8 °C)
07 21.2 °F (-6 °C)
08 24.8 °F (-4 °C)
17) Outdoor temperature zone boundary temperature B
Setting required if changing of the outdoor temperature setting for heat pump only zone is required
when auxiliary heater control by outdoor temperature 1 is performed on the indoor unit. For details,
refer to “External heater output” on page 2.
Function number Setting value Setting description Factory setting
67
00 42.8 °F (6 °C)
01 14.0 °F (-10 °C)
02 17.6 °F (-8 °C)
03 21.2 °F (-6 °C)
04 24.8 °F (-4 °C)
05 28.4°F (-2 °C)
06 32.0 °F (0 °C)
07 35.6 °F (2 °C)
08 39.2 °F (4 °C)
09 42.8 °F (6 °C)
10 46.4 °F (8 °C)
11 50.0 °F (10 °C)
12 53.6 °F (12 °C)
13 57.2 °F (14 °C)
14 60.8 °F (16 °C)
15 64.4 °F (18 °C)
- 75 -
9-2. Contents of function setting 9. Function settings
CASSETTE TYPE
AUU18-48RGLX
CASSETTE TYPE
AUU18-48RGLX