• Forced thermostat off function
Function
setting /
Rotary SW on
External Input and
Output PCB
External input Input signal Command
60-00 / 2
60-09 / B
60-10 / C
External Input and Output
PCB
CN313
Off → On
Thermostat
off
On → Off
Normal
operation
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
NOTE: When the signal is received from another unit on the refrigerant circuit, there may be a de-
lay in thermostat off function at the unit.
- 138 -
12-2. Wall mounted type (KGTB, KETA, and KETA-B) 12. External input and output
2-UNIT
MULTI-SPLIT TYPE
2-UNIT
MULTI-SPLIT TYPE