External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
Indoor unit
A twisted pair cable should be used. Maximum length of cable is 25 m.
Output voltage: High DC 12 V ± 2 V, Low 0 V.
Permissible current: 50 mA
For details, refer to "Combination of external input and output" on page 150
When indicator or other components are connected directly
Example: Function setting 60 is set to "00"
1
2
Connector
(CN47)
LED
PCB
Resistor
Connected unit
+
-
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00"
1
2
Connected device
Connector
(CN47)
PCBConnected unit
Relay
(Operation status)
-
+
- 148 -
12-4. Wall mounted type (KGTE, KGTF, KMCE, KMCF, KETE, KETE-B, KETF, and KETF-
B)
12. External input and output
2-UNIT
MULTI-SPLIT TYPE
2-UNIT
MULTI-SPLIT TYPE