1-5. Rotation number of compressor limitation by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
• Cooling/Dry mode
B zone
A zone
7°C
C zone
18°C
D zone
38°C
Unit: rps
Model name Outdoor temperature zone
Limitation of compressor
rotation number
AOYG18KBTA3
AOYG24KBTA3
A zone 20
B zone 19
C zone 14
D zone 20
• Heating mode
D zone
5°C
C zone
B zone
A zone
-1°C
-6°C
Unit: rps
Model name Outdoor temperature zone
Limitation of compressor
rotation number
AOYG18KBTA3
AOYG24KBTA3
A zone 40
B zone 35
C zone 26
D zone 14
1-5. Rotation number of compressor limitation by outdoor temperature - (04-19) - 1. Rotation number control of compressor