8) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of the room temp. sensor - Correction temp. value
Example of correction:
When the temperature of the room temp. sensor is 26°C and the setting value is “03”
(-1.0°C), corrected temp. will be 27°C (26°C - [-1.0°C]).
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting
01 No correction 0.0 °C
02 -0.5 °C
More cooling
Less heating
03 -1.0 °C
04 -1.5 °C
05 -2.0 °C
06 -2.5 °C
07 -3.0 °C
08 -3.5 °C
09 -4.0 °C
10 +0.5 °C
Less cooling
More heating
11 +1.0 °C
12 +1.5 °C
13 +2.0 °C
14 +2.5 °C
15 +3.0 °C
16 +3.5 °C
17 +4.0 °C
- 272 -
14-5. Function details 14. Function settings
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE