End
Check Point 2 : Wire installation wrong remote controller group setting
Wrong wire connection in remote controller group (Please refer to the installation manual)
The number of connecting indoor unit and remote controller in one remote controller group
were less than 16 units.
Check Point 2-1 : Check Indoor unit main PCB
Check if main PCB damage
Change main PCB and check the error after setting remote controller address
End
2-3. E: 12. Wired remote controller communication error (Indoor unit) - (03-16) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING