EasyManuals Logo

Fujitsu AUXG12KVLA Service Instruction

Fujitsu AUXG12KVLA
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation fre-
quency of compressor.
If the room temperature is 6.0 °C lower than a set temperature, the compressor operation frequen-
cy will attain to maximum performance.
If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
compressor frequency is controlled within the range shown below.
Compressor frequency range
Unit: rps
Model name Minimum frequency Maximum frequency
AUXG09KVLA 14 110
AUXG12KVLA 14 110
AUXG14KVLA 12 110
AUXG18KVLA 12 110
AUXG22KVLA 8 120
1-2. Heating operation - (04-3) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Other manuals for Fujitsu AUXG12KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG12KVLA and is the answer not in the manual?

Fujitsu AUXG12KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG12KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals