SERVICE PARTS INFORMATION 8
Thermistor
02-41
Check Point : Check Thermistor resistance value
Remove connector and check Thermistor resistance value.
Temperature
[°C]
Resistance Value [ k ]
Thermistor A Thermistor B Thermistor C
Applicable
Thermistors
Discharge temp. TH Outdoor temp. THHeat exchanger. TH
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100
110
120
1013.1
531.6
292.9
168.6
100.9
62.5
40.0
26.3
17.8
12.3
8.7
6.3
4.6
3.4
2.6
2.0
95.6
50.3
27.8
16.1
9.6
6.0
3.8
2.5
1.7
1.2
0.8
0.6
---
---
---
---
224.3
115.2
62.3
35.2
20.7
12.6
8.0
5.2
3.5
2.4
---
---
---
---
---
---