Indoor unit
type
Model name PCB* fuse Fan motor thermal protector
Terminal
thermal
fuse
Float
switch
Wall mounted
ASYG07KGTB
250 V, 3.15 A
Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
102 °C Off ―
ASYG09KGTB
ASYG12KGTB Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG14KGTB
ASYG07KGTE Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
ASYG09KGTE
ASYG12KGTE Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG14KGTE
ASYG07KGTF Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
ASYG09KGTF
ASYG12KGTF Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG14KGTF
ASYG18KMTB Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG22KMTB
ASYG24KMTB
ASYG18KMTE Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG22KMTE
ASYG24KMTE
ASYG07KMTB Activate: More than 95 °C
Fan motor speed down
Reset: 95 °C or less
Fan motor speed recover
ASYG09KMTB
ASYG12KMTB
ASYG14KMTB
Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
- 184 -
11. Safety devices
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE