Details of control input function

Operation/Stop mode 1
• In the case of "Edge" input
Function
setting
External Input and
Output PCB
External input Input signal Command
Rotary
switch
SW2
46-00
— Input of indoor unit Terminal
Off → On Operation
On → Off Stop
1 Edge
External Input and
Output PCB
Ex IN 1
Off → On Operation
On → Off Stop
Remote controller
On
Off
Indoor unit operation
On
Ex IN 1
On
Off
• In the case of "Pulse" input
Function
setting
External Input and
Output PCB
External input Input signal Command
Rotary
switch
SW2
46-00 1 Pulse
External Input and
Output PCB
Ex IN 1
Pulse
Operation
Ex IN 2 Stop
On
Remote controller
On
Off
Indoor unit operation
Ex IN 1
On
Off
On
Off
Ex IN 2
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.
- 191 -
12-1. Compact cassette type, Medium static pressure duct type (ARXH22KMTAP), and
Ceiling type
12. External input and output
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE

Table of Contents

Other manuals for Fujitsu AUXG14KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG14KVLA and is the answer not in the manual?

Fujitsu AUXG14KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG14KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals