UTY-RVNYM
Function setting procedure
1. Connect the power supply of the outdoor unit.
2. Switch to the function setting mode.
When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the
“Submenu” screen. If [Menu button] is pressed while the “Submenu” screen is displayed, the
display returns to the “Monitor” screen.
Back:
Setting:
Date and time
Submenu
[
1/2
]
Monitor
Screen
Filter sign
R.C. sensor control
Room temp. display
Off
Off
Mo
10:00AM
Menu
Monitor
O f f
Mo
10:00
AM
Press the [Screen switch button (Left)] and [Screen switch button (Right)] simultaneously for 5
seconds to switch to “Service” screen.
Back
:
Se tt ing :
Service
Mo
10:00AM
Fun c tion sett in g
Error hi stor y
I.U.a ddre ss ver if ic at io n
V e rs i o n
Test run
Back:
Setting:
Date and time
Submenu
[
1/2
]
Monitor
Screen
Filter sign
R.C. sensor control
Room temp. display
Off
Off
Mo
10:00AM
Select [Function setting] with pressing the [Cursor button (Up/Down)], and press the [Enter but-
ton].
Back
:
Settin g :
Service
Mo
10:00AM
Fu nc t io n s et t in g
Error h ist or y
I.U.ad dr ess ve r i f i ca t i o n
V e r s i o n
Test run
C
ancel
:
OK :
Function s etti ng
Mo
10:00AM
R.C. Function Setting
address No. No.
00
00
00
Version E rro r hi st ory
- 322 -
15-4. Indoor unit (setting by wired remote controller)
15. Function settings
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE