2-12. E: 39. Indoor unit power supply error for fan motor (Indoor
unit)
Indicator Indoor unit
Operation indicator 3 time flash
Timer indicator 9 time flash
Economy indicator Continuous flash
Error code E: 39
Detective actuator Indoor unit main PCB
When a momentary power cut off
When do not start fan motor
Forecast of cause
External cause
Connector connection failure
Main PCB failure
Check point 1. Check external cause at indoor and outdoor (Voltage drop or Noise)
Instant drop: Check if there is a large load electric apparatus in the same circuit.
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check point 2. Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
→ Upon correcting the removed connector or mis-wiring, reset the power.
Check point 3. Replace the main PCB
If check point 1 to 2 do not improve the symptom, replace the main PCB.
End
2-12. E: 39. Indoor unit power supply error for fan motor (Indoor unit) - (03-25) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AUXG14KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG14KVLA and is the answer not in the manual?

Fujitsu AUXG14KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG14KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals