2-19. E: 53. Drain pump error (Indoor unit)
Indicator Indoor unit
Operation indicator 5 time flash
Timer indicator 3 time flash
Economy indicator Continuous flash
Error code E: 53
Detective actuator
Indoor unit main PCB
When Float switch is ON for more than 3 minutes.
Float switch
Forecast of cause
Float switch failure
Shorted connector/wire failure
Main PCB failure
Drain pump failure
Hose clogging
Check point 1. Check float switch
Check operation of float switch. (any blocking by dust, etc.)
Remove float switch and check ON/OFF switching operation by using a meter.
-> If float switch is abnormal, replace it.
Check point 2. Check connector and wire
Check loose contact of CN9 and shorted wire (pinched wire).
-> Replace float switch if the wire is abnormal
Check point 3. Check drain hose
Check drain hose.
-> If there is hose clogging. Please clear the clog.
Check point 4. Replace the main PCB
If check point 1 to 3 do not improve the symptom, replace the main PCB and execute the check
operation again.
End
Attention
Wall mount type does not have a float switch. In this case, replace main PCB and set up the origi-
nal address.
2-19. E: 53. Drain pump error (Indoor unit)
- (03-32) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AUXG14KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG14KVLA and is the answer not in the manual?

Fujitsu AUXG14KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG14KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals