EasyManua.ls Logo

Fujitsu AUXG14KVLA - Page 37

Fujitsu AUXG14KVLA
403 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation space
Unit: mm
100 or more
80 or more
80 or more
150 or below from the floor
50 or more
Grating
PROHIBITED
WARNING
The appliance shall be installed, operated and stored in a room with a floor area larger than X
m
2
.
Amount of refrigerant charge
M (kg)
Minimum room area
X (m
2
)
M ≤ 1.22 -
1.22 < M ≤ 1.23 12.99
1.23 < M ≤ 1.50 19.31
1.50 < M ≤ 1.75 26.28
1.75 < M ≤ 2.0 34.33
2.0 < M ≤ 2.5 53.63
2.5 < M ≤ 3.0 77.23
3.0 < M ≤ 3.5 105.12
3.5 < M ≤ 4.0 137.29
(IEC 60335-2-40)
2-5. Floor type
- (01-31) - 2. Dimensions
GENERAL
INFORMATION
GENERAL
INFORMATION

Table of Contents

Other manuals for Fujitsu AUXG14KVLA

Related product manuals