5) Static pressure (for Mini duct type and Slim duct type)
Select the appropriate static pressure according to the installation conditions.
For mini duct type:
Function number Setting value Setting description Factory setting
26
00 0 Pa
01 10 Pa
02 20 Pa
03 30 Pa
04 40 Pa
05 50 Pa
31
Standard
(10 Pa: 07; 09; 12 models, 15 Pa: 14; 18
models)
NOTES:
Range of static pressure is different by model.
Model Range of static pressure
07, 09, 12 models 0 to 30 Pa
14 model 0 to 50 Pa
Setting number in 07, 09, 12 models is “04 to 30”: Operation is same as that “03”.
Setting number in 14 model is “06 to 30”: Operation is same as that “05”.
Setting number value cannot be set to 32 or more.
For slim duct type:
Function number Setting value Setting description Factory setting
26
00 0 Pa
01 10 Pa
02 20 Pa
03 30 Pa
04 40 Pa
05 50 Pa
06 60 Pa
07 70 Pa
08 80 Pa
09 90 Pa
31 Standard (25 Pa)
1-5. Function details - (05-42) - 1. Function settings (for indoor unit)