EasyManua.ls Logo

Fujitsu AUXG24KVLA - 8-6. Indoor unit (setting by wired remote controller)

Fujitsu AUXG24KVLA
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢ Model: AOHG36KRTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 3.5 A 3.0 A
50°C ≤ Ta < 52°C 5.5 A 5.0 A
42°C ≤ Ta < 50°C 6.0 A 5.5 A
2°C ≤ Ta < 42°C 7.5 A 7.0 A
Ta < 2°C 8.5 A 8.0 A
Heating
20°C ≤ Ta 5.5 A 5.0 A
16°C ≤ Ta < 20°C 6.0 A 5.5 A
12°C ≤ Ta < 16°C 7.0 A 6.5 A
2°C ≤ Ta < 12°C 7.5 A 7.0 A
Ta < 2°C 8.5 A 8.0 A
¢ Models: AOHG45KRTA and AOHG54KRTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 4.5 A 4.0 A
50°C ≤ Ta < 52°C 5.5 A 5.0 A
46°C ≤ Ta < 50°C 6.5 A 6.0 A
42°C ≤ Ta < 46°C 7.5 A 7.0 A
2°C ≤ Ta < 42°C 8.5 A 8.0 A
Ta < 2°C 10.0 A 9.5 A
Heating
20°C ≤ Ta 6.5 A 6.0 A
16°C ≤ Ta < 20°C 7.0 A 6.5 A
12°C ≤ Ta < 16°C 8.0 A 7.5 A
2°C ≤ Ta < 12°C 8.5 A 8.0 A
Ta < 2°C 10.0 A 9.5 A
8-3. Current release control - (04-35) - 8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Other manuals for Fujitsu AUXG24KVLA

Related product manuals