2005.08.01
1
SPECIFICATIONS
TYPE COOLING COOLING & HEATING
INDOOR UNIT
AUY36FUAS AUY36UUAS
OUTDOOR UNIT AOY36FNAXT AOY36UNAXT
COOLING CAPACITY
(kW)
10.5 10.5
HEATING CAPACITY
(kW)
------- 11.80
POWER SOURCE
FREQUENCY
50Hz
COOLING 6.20 5.90
RUNNING CURRENT
(A)
HEATING ------- 6.20
INPUT WATTS
(kW)
COOLING 3.74 3.48
HEATING ------- 3.65
E.E.R. (kW/kW)
COOLING 2.81 3.02
HEATING ------- 3.23
STARTING CURRENT (A) 37
MOISTURE REMOVAL
4.0
3N 400V
TYPE
Hermetic type, 2 poles, 3 phase,
Induction motor, Twin Rotary
DISCRIMINATION 5JD420PAA02
REFRIGERANT R410A (g) 2,000 3,200
ELECTRICAL DATA
COMPRESSOR
( /hr)
ADDITIONAL REFRIGERANT CHARGE (R410A)
PIPE LENGTH
20 m
2,000 g 3,200 g
FULL CHARGE AMOUNT
30 m
2,300 g 3,500 g
40 m
2,600 g 3,800 g
50 m
2,900 g 4,100 g
ADDITIONAL CHARGE 30 g / m
HIGH 560
INDOOR
MED 490
FAN SPEED
LOW 420
(r.p.m.)
S-LOW 300
OUTDOOR 780
AIR FLOW
INDOOR 1,500 (HIGH)
(m
3
/h)
OUTDOOR 7,000 6,100
DIMENSIONS
INDOOR 296 x 830 x 830
GRILLE 35 x 940 x 940
H x W x D (mm)
OUTDOOR 1,165 x 900 x 330
WEIGHT
INDOOR
37 / 52
[NET/GROSS] (kg)
OUTDOOR 80 / 87 94 / 101
MAX PIPE LENGTH / HEIGHT (m)
50 / 30
REMOTE CONTROLLER TYPE WIRED