EasyManua.ls Logo

Fujitsu General AOHG12KMCC - Capacity Compensation Rate for Pipe Length and Height Difference; Models: AOHG07 KMCC and AOHG09 KMCC

Fujitsu General AOHG12KMCC
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Models: AOHG07KMCC and AOHG09KMCC
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.872 0.910
10 0.961 0.886 0.925
7.5 0.979 0.965 0.890 0.929
5 0.992 0.983 0.969 0.893 0.933
0 1.000 0.991 0.976 0.901 0.940
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.991 0.976 0.901 0.940
-7.5 0.991 0.976 0.901 0.940
-10 0.976 0.901 0.940
-15 0.901 0.940
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.832 0.822
10 0.917 0.832 0.822
7.5 0.961 0.917 0.832 0.822
5 1.000 0.961 0.917 0.832 0.822
0 1.000 0.961 0.917 0.832 0.822
Indoor unit is lower than
outdoor unit *2
-5 0.955 0.956 0.912 0.828 0.818
-7.5 0.954 0.910 0.826 0.816
-10 0.908 0.824 0.814
-15 0.815 0.805
- 49 -
6-1. Models: AOHG07KMCC and AOHG09KMCC 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG07-14KMCC
OUTDOOR UNIT
AOHG07-14KMCC