7. Additional charge calculation
7-1. Models: AOHG07KMCC and AOHG09KMCC
Refrigerant type R32
Refrigerant amount g 600
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
7-2. Model: AOHG12KMCC
Refrigerant type R32
Refrigerant amount g 700
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
7-3. Model: AOHG14KMCC
Refrigerant type R32
Refrigerant amount g 850
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
- 51 -
7-1. Models: AOHG07KMCC and AOHG09KMCC 7. Additional charge calculation
OUTDOOR UNIT
AOHG07-14KMCC
OUTDOOR UNIT